Beyond PUE – What Makes a Data Center Truly Sustainable? An Interview with Dr. Jon Summers

Beyond PUE – What Makes a Data Center Truly Sustainable? An Interview with Dr. Jon Summers 714 445 H1 Systems Mérnöki Szolgáltatások Kft.

Why is liquid cooling so efficient in data centres and what is the best coolant? What are the best sustainability metrics for data centres today? Is a data centre less energy efficient than an incandescent light bulb? Jon Summers, Scientific Lead in Data Centres at Research Institutes of Sweden (RISE), Adjunct Professor of Fluid Mechanics at Lulea Technical University in Sweden and Visiting Professor of Thermofluids at the University of Leeds, answered our questions at the H1 Systems DC Meetup in Budapest.

In some of the previous blog articles, we have covered the Research Institutes of Sweden (RISE), but for the possible new readers, can you just say a few sentences about it? What is the main area of activity there and what are the main achievements?

RISE is a very large research organisation, and it covers a lot of disciplines in science and engineering. The unit that I work for, is focused on data centres, our job is to look at operational efficiency and to look into rigorous testing and validation of some of the new equipment that’s being used in data centres now, particularly on the cooling side of things. We’re going back to liquid cooling now. It’s like going back to the future, isn’t it?

RISE is focused on sustainability and operational efficiency and future technologies. And it’s all about IT. I mean, we don’t really work with what’s happening in IT. It’s a field that we don’t have a lot of control over. But what you put around it, the system you put around IT, is where our research focus is. And we’re part of the Digital Systems Division, which has a computer science department. And the ICE Data Centre unit is part of that computer science department.

Jon Summers at the 3rd H1 DC Meetup in Budapest, February 26th, 2025


Talking about liquid cooling and the ‘back to the future’ effect, can you summarise the concept and give us some ideas on the best cooling fluids?

One of the speakers at the meetup mentioned in his presentation that Lenovo was using de-ionized water for their direct-to-chip system. And NVIDIA is pushing PG25, which is propylene glycol, 25 per cent glycol with water, with additives. This is for direct-to-chip systems, but you have to remember that we have to make the system completely watertight. Because if any of that leaks onto the IT equipment, the very, very, very expensive IT equipment, it can damage it. One aspect of it is that we’re using coolants which, if they leak, can damage the IT equipment.

The two-phase direct-to-chip system, which was also mentioned, is another way of doing direct-to-chip liquid cooling. There are two reasons why you use a liquid that changes phase. On the one hand, it usually improves the heat transfer because – this is on the diagrams that I had in my presentation – the thermal resistance goes down, so it’s got a much wider range of extracting the heat. The other thing is that it’s usually a dielectric, so if it leaks it’s not going to damage the IT equipment.

That’s the dilemma from the direct-to-chip side. If you go single-phase, you’re probably going to be using a water-based system, and you really have to be careful about leaks. Some manufacturers have looked at this and said, well, can we run it under pressure so that if there is a break in the hose or a crack, instead of liquid coming out, it sucks in air. It’s not the liquid that comes out or the water that comes out, it’s the air that’s sucked in and then you can fix the problem.

But that’s one class of liquid cooling. There’s another class of liquid cooling, which is called immersion liquid cooling, where you put all the electronics, even the power supplies, into a dielectric liquid. That’s not guaranteed by NVIDIA, so the reason it’s not happening a lot with AI now is because, as I understand it, NVIDIA won’t say they’re going to guarantee their equipment for immersion. And there are other complexities and physical complexities like what we call signal integrity, to put it differently what happens because the signals between the GPUs go over a very fast interconnect. And sometimes we don’t know how well that works when it’s submerged. That’s a piece of research that’s going on right now.


We have heard a lot, even here today, about PUE as a key metric for data centre efficiency. Can you summarise your view on data centre sustainability metrics?
PUE, power usage effectiveness, along with a couple of other metrics like water usage effectiveness and so on, are classified as sustainability metrics, but they don’t really tell you the whole story. PUE is an interesting metric. It was first introduced in a paper at a conference in 2006 by Belady and Malone, who were working for HP at the time. That was before the Green Grid picked it up. They wrote a paper saying it was a ratio of two powers. They monitored it at a point in time and calculated it as the power consumption of the whole data centre divided by the power consumption of the IT.

Then they realised later, when it went to the Green Grid, that this value is very much affected by the season, by the temperature outside. Because your cooling infrastructure requirements change as the seasons change, the energy consumption of the cooling infrastructure is very much linked to the outside temperature. This is why they decided that this should be measured over a whole year, and it became what’s called an annualised metric.

The thing that PUE has done is that it has helped data centres improve their performance. I don’t think it’s a very good metric for comparing data centres. However in the 2006 paper, it said that government agencies like the EPA – the Environmental Protection Agency – could use this metric to justify building the data centres. And it was a metric that was used to mandate building data centers in geographic locations like Amsterdam, Singapore and other locations.

But a target PUE makes it a bit divisive because you have very different climates, very different environmental conditions. And it’s also very complex because even in my presentation I showed how IT can use more power if you run hotter. And of course ASHRAE (the American Society of Heating, Refrigerating and Air-Conditioning Engineers) has said run your IT hotter. You’re using more power on the IT side, but then you’re using less power on the cooling side, so your PUE is going in the right direction: it’s going down. But are you using less energy or more energy? I think sustainability metrics should focus first on what is the data centre doing or what’s the productivity of the data centre. And then how much is that costing us in terms of kilowatt-hours of electrical energy.

Jon Summers at the 3rd H1 DC Meetup in Budapest, February 26th, 2025

And the other thing is the cooling system supported by the use of water. It’s fine if it’s in a geographical location where there’s no water stress, but if it’s in a location where there is water stress, then the environmental impact is so much higher. Water efficiency metric, if you want to use it as a sustainability metric, depends on where the water is being used. Because it doesn’t really matter if you’re using half a litre per kilowatt hour in a place where there’s no stress on the water system. But at the end of the day, if you’re using potable water, there’s energy associated with that too. That is not factored into the PUE because it measures the energy, or the ratio of electrical energies.


When you talked about energy consumption and energy efficiency in your presentation, you made a very interesting comparison between chips and light bulbs. Could you summarise that for our readers?
You’re putting energy into the system, and that energy is designed to produce digital information. There’s a scientific approach to measuring the energy value of the information. And if you measure that energy value today, it’s about 0.03% of the energy consumed from the grid that goes into the information. That’s the part you want.

You must pay for every kilowatt hour that the data centre uses. And what you want is a digital service that uses only 0.03% of the energy associated with the data centre. About 99.97% of the energy goes into heat, and that is a problem. The incandescent light bulb was banned because it was so inefficient. Only 5% of the energy went into the light, which is what you want, but you’ve got to pay for the electricity, the power for the light. And what you want is the light, but if you’re only getting 5% of it, it’s not very efficient. It really demonstrates the fact that data centres, if you look at them in their pure form, what you want divided by what you have to pay for, demonstrates that they’re very inefficient, energy inefficient.